PVC Conduit 20, 25 and 32 mm: How Many Wires Fit, and When Should You Size Up?

اقرأ هذا المقال بالعربية

How many wires fit in 20, 25 and 32 mm electrical PVC conduit? A capacity table for each wire size at 40% fill, when to size up, and conduit prices including 15% VAT from Almadah's catalogue as of 22/11/2026.

PVC Conduit 20, 25 and 32 mm: How Many Wires Fit, and When Should You Size Up?

Short answer: At 40% fill, a 20 mm heavy-gauge PVC conduit takes about 8 wires of 1.5 mm² or 6 wires of 2.5 mm². A 25 mm conduit takes about 14 and 10, and a 32 mm conduit about 23 and 17. Size up as wires get larger or more numerous, or when the run is long with many bends.

How many wires fit in 20, 25 and 32 mm PVC conduit?

The table gives the maximum number of single-core PVC-insulated wires (450/750 V) in heavy-gauge conduit at 40% fill of the internal cross-section. Internal diameter = outer diameter minus twice the wall thickness. Wall thicknesses come from the Bahra product names in Almadah's catalogue (1.8 mm for 20 mm, 1.9 mm for 25 mm, 2.5 mm for 32 mm).

Conduit sizeApprox. internal diameter1.5 mm²2.5 mm²4 mm²6 mm²10 mm²
20 mm16.4 mm86432
25 mm21.2 mm1410763
32 mm27.0 mm231712106

How it is calculated: count = (40% x internal cross-section area) / (wire cross-section area including insulation), rounded down. We assumed these maximum outer diameters for flexible wire: 3.5 mm (1.5 mm²), 4.1 mm (2.5 mm²), 4.8 mm (4 mm²), 5.3 mm (6 mm²) and 6.8 mm (10 mm²). They vary slightly between manufacturers, so check the datasheet of the wire you will actually pull. Medium-gauge conduit has a thinner wall, which adds one or two wires in some cells.

Bahra 20 mm black heavy-gauge PVC conduit

*Bahra 20 mm heavy-gauge PVC conduit, one of the best-selling conduits in the category.*

Why design for 40% fill instead of filling the conduit?

Wires are pulled after the conduit is installed, and they heat up in service. A packed conduit makes pulling hard, can scrape the insulation, traps heat, and leaves no room to add a wire later. 40% is the common design fill for three or more conductors, and it is the basis of the table. The figure that applies to your project is set by the Saudi Electrical Code and your consultant's specification, so follow those if they differ.

How do I size a conduit that carries wires of different sizes?

The table assumes one wire size. For a mix:

  • Add up the wire areas: each wire's area = 0.785 x (outer diameter)². A 2.5 mm² wire at 4.1 mm is about 13.2 mm², and a 1.5 mm² wire at 3.5 mm is about 9.6 mm².
  • Work out the conduit capacity: 40% of its internal area. A 20 mm conduit (16.4 mm inside) has 211 mm² and a capacity of 84 mm²; a 25 mm conduit has 353 mm² and 141 mm²; a 32 mm conduit has 573 mm² and 229 mm².
  • Compare: if the wire total is below capacity, the size works. Example: 3 wires of 2.5 mm² + 2 wires of 1.5 mm² = 39.6 + 19.2 = 58.8 mm², within 84 mm², so a 20 mm conduit is enough.
  • Do not forget the earth conductor: count it with the rest, since it takes up space too.

When should I move from 20 mm to 25 mm, and from 25 mm to 32 mm?

Size up in these cases:

  • Over capacity: the wire areas exceed 40% of the conduit cross-section.
  • Long run or many bends: pulling gets harder at every elbow, so go above the calculated minimum rather than sitting on it.
  • Wires larger than 4 mm²: 20 mm conduit loses capacity fast (only two 10 mm² wires), so use 25 or 32 mm.
  • Planned additions: if points will be added later, leave room now.
  • Several circuits in one conduit: avoid it where possible; one conduit per circuit is better, and any grouping is for your consultant to decide.

The price step is small compared with the cost of re-pulling. From Almadah's catalogue (as of 22/11/2026, including 15% VAT): a Bahra heavy-gauge 2.9 m conduit costs SAR 4.52 in 20 mm, SAR 6.31 in 25 mm and SAR 10.36 in 32 mm.

Bahra 25 mm black heavy-gauge PVC conduit

*Bahra 25 mm heavy-gauge PVC conduit.*

Which size suits lighting, sockets and air conditioners?

A common choice for residential first-fix, to be checked with your consultant and each circuit's load:

CircuitUsual wire sizeSize that usually works
Lighting1.5 mm²20 mm (up to about 8 wires)
General sockets2.5 mm²20 mm for one circuit, 25 mm when grouped
AC unit or water heater on 4 or 6 mm² wire4 – 6 mm²25 mm
Main feeder on 10 mm² or larger10 mm² and up32 mm and above, or a larger conduit

This is general first-fix guidance. It does not replace load calculations or a check against the Saudi Electrical Code.

Bahra 32 mm black heavy-gauge PVC conduit

*Bahra 32 mm heavy-gauge PVC conduit.*

How much does 20, 25 and 32 mm PVC conduit cost?

As of 22/11/2026, including 15% VAT, the price range for a full conduit length (all grades and brands) in Almadah's catalogue:

SizePrice range (SAR)
20 mm2.13 – 4.89
25 mm4.20 – 6.31
32 mm6.44 – 12.54

Across the whole "Conduits and Electrical Raceways" category, the median item price is SAR 32.44 (the range runs from SAR 0.16 for the smallest accessory up to large industrial items), and the median for "PVC Conduit and Boxes" is SAR 31.05. We use the median because large industrial items distort the arithmetic mean. The category's top sellers are Bahra 20 and 25 mm heavy-gauge conduit, plus the elbows and boxes that match them. Prices move as suppliers update, so confirm on the product page when you buy.

FAQ

How many 2.5 mm² wires fit in a 20 mm PVC conduit?

About 6 at 40% fill in heavy-gauge conduit, with 10 in 25 mm and 17 in 32 mm.

Is 20 mm conduit enough for a lighting circuit?

Usually yes. It takes about 8 wires of 1.5 mm², which covers a typical lighting circuit with its earth. If the run is long or has many bends, use 25 mm.

Why not fill the conduit with as many wires as possible?

Pulling becomes difficult, insulation can be damaged, heat builds up inside, and there is no room to add a wire later.

Do I count the earth wire?

Yes. It occupies space in the cross-section like any other conductor.

Is 25 mm conduit suitable for an air conditioner?

Usually, with 4 or 6 mm² wire (7 or 6 wires at most by calculation). The wire size depends on the unit's load and the run length, so confirm with your consultant.

What is the difference between medium- and heavy-gauge conduit?

Wall thickness and impact resistance. Heavy-gauge is thicker and withstands knocks and pours better; medium-gauge has a thinner wall, so it holds slightly more and costs less.

Is the calculation different for multicore cable?

Yes. A cable's outer diameter is larger than the sum of its cores because of the sheath. Use the cross-section of the cable itself from its datasheet.

Conclusion

At 40% fill: 20 mm conduit takes about 8 wires of 1.5 mm² or 6 of 2.5 mm², 25 mm about 14 and 10, and 32 mm about 23 and 17. Add up the wire areas when sizes are mixed, size up for long runs and many bends, and check the fill limit in the Saudi Electrical Code and your project specification. The category median price is SAR 32.44 including VAT (22/11/2026).